What ASTM F2170 and F1869 Actually Measure
ASTM F2170 and ASTM F1869 answer two different questions about the same slab. F2170, formally the “Standard Test Method for Determining Relative Humidity in Concrete Slabs Using in situ Probes,” measures the percentage of relative humidity inside the concrete mass, at a depth that represents how the slab will behave once it’s covered. F1869, the “Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride,” measures how much moisture vapor is leaving the top surface of the slab over a fixed time window, expressed in pounds per 1,000 square feet per 24 hours.
That distinction sounds academic until you’re staring at a spec sheet and a flooring warranty that don’t agree. F1869 tells you what’s happening at the surface, right now, under lab-controlled ambient conditions. F2170 tells you what’s happening deep in the slab, where moisture is still migrating outward and where it will keep affecting an adhesive or coating long after installation day. One is a snapshot. The other is closer to a forecast.
F1869: The Calcium Chloride Test, Process and Limitations
ASTM F1869 places a dish of anhydrous calcium chloride on the slab surface, seals it under a plastic dome, and leaves it undisturbed for 60 to 72 hours. The calcium chloride absorbs ambient moisture vapor; the weight gain is converted into a moisture vapor emission rate (MVER) in lbs/1,000 sq ft/24 hr. It’s a well-understood, inexpensive test with decades of field history.
Its limitations are just as well documented. Because the dome only captures the top few millimeters of slab behavior, F1869 results shift with ambient humidity, temperature, and even the time of year the test is run. A test performed during a dry, heated winter can read differently than the same slab tested in a humid summer, even though the concrete’s actual internal moisture condition hasn’t changed. The test also can’t account for moisture still migrating upward from lower in the slab, which is precisely the moisture that causes adhesive failures and flooring blisters months after installation. Industry sources have flagged these sensitivity issues as a core reason MVER results are treated with caution on moisture-sensitive jobs.
F2170: In-Situ Relative Humidity Testing, Process and Field Practice
F2170 requires drilling probe holes to 40% of the slab’s thickness for slabs drying from one side, inserting sensor sleeves, sealing them, and waiting a minimum 24 hours for the sensors to equilibrate with the surrounding concrete before taking a hygrometer reading. The 40% depth isn’t arbitrary. It corresponds to the point in the slab profile where moisture conditions best predict what will reach the top surface once a floor covering traps vapor from escaping.
Hole spacing follows a minimum-density rule: three probe locations for the first 1,000 square feet of slab, with one additional probe for each additional 1,000 square feet. That density matters because concrete moisture is rarely uniform across a large pour, so a single reading in a 50,000-square-foot warehouse floor tells you almost nothing. A properly executed F2170 test on that floor would call for roughly 53 individual probe locations, each equilibrated and read independently.
The 24-hour equilibration window is where field shortcuts happen, and where results go wrong. A probe read at hour 12 instead of hour 24 will almost always read lower than its true equilibrium value, because the sensor hasn’t fully stabilized to the surrounding concrete’s humidity. If you’re reviewing someone else’s F2170 report, the equilibration timestamps and hole-count math are the first two things worth checking.
Why the Industry Has Shifted Toward RH Testing
ASTM has formally moved away from calcium chloride testing for certain slab types. Amendments to F1869 removed the calcium chloride method as an acceptable means of measuring moisture in lightweight concrete, while F2170 was developed specifically to recognize in-situ relative humidity testing as an integral assessment method for those same slabs. Calcium chloride reads surface evaporation; RH testing reads the moisture condition at 40% depth, which is the profile lightweight aggregate concrete needs evaluated correctly because of how it retains and releases water differently than normal-weight concrete.
That standards-level shift has pushed through to the commercial side. Most flooring and adhesive manufacturers now specify in-situ RH data, sometimes exclusively, as the acceptable moisture documentation for warranty coverage. If you install a resinous coating or a moisture-sensitive adhesive system based on an F1869 reading when the manufacturer’s warranty language calls for F2170 data, you may have a compliant-looking test report and an unenforceable warranty at the same time.
F2170 vs. F1869: Side-by-Side Comparison
The table below lines up the two standards on the variables that actually drive spec decisions: what’s measured, how it’s measured, and where each one still applies. Use it to check a test report against the method a project spec or warranty actually calls for.
| Factor | ASTM F2170 | ASTM F1869 |
|---|---|---|
| What it measures | Internal relative humidity at 40% slab depth | Surface moisture vapor emission rate (MVER) |
| Units | Percent relative humidity (%RH) | lbs/1,000 sq ft/24 hr |
| Test duration | 24-hour minimum equilibration, then read | 60-72 hour sealed dome test |
| Sensitivity to ambient conditions | Lower; measures internal slab condition | Higher; affected by ambient temp/humidity |
| Probe/test density | 3 per first 1,000 sq ft, +1 per additional 1,000 sq ft | 1 per 1,000 sq ft (typical practice) |
| Accepted for lightweight concrete | Yes, standard method | No, removed from scope |
| Manufacturer warranty preference | Increasingly required or preferred | Accepted by fewer manufacturers over time |
Which Test Fits Which Project?
Neither standard is universally “better.” Each fits specific project conditions, and the right choice depends on slab type, spec language, and how moisture-sensitive the finished floor system is.
New construction with lightweight or structural concrete over metal deck should default to F2170; it’s the only method ASTM currently accepts for that slab type, and most manufacturer warranties on these projects require RH data outright. High-risk installations, resinous flooring, moisture-sensitive adhesives, healthcare and cleanroom environments, and any high-bay warehouse floor supporting racking or automated storage systems all carry enough consequence that F2170’s deeper, more stable reading is worth the extra field time. Legacy specifications written before the industry’s shift toward RH testing may still reference F1869 by name; in those cases, follow the governing spec and document the method used clearly, since retrofitting a different test after the fact can create its own compliance headache. F1869 still has a legitimate role on lower-risk slabs, quick preliminary screening, or projects where the governing spec explicitly calls for MVER data and the concrete is conventional weight, not lightweight.
When a spec is silent or ambiguous on method, that’s a flag to raise with the design team before testing starts, not after. A pre-installation moisture testing plan that names the standard, the probe count, and the acceptance criteria in writing protects everyone on the job, including the testing firm.
Why You Can’t Convert or Cross-Walk Results Between Tests
There is no accepted conversion factor between an F1869 MVER number and an F2170 relative humidity percentage, and treating them as interchangeable data points is a documented source of spec and warranty disputes. The two tests aren’t measuring the same physical phenomenon at the same location in the slab; one is surface evaporation under a sealed dome, the other is internal humidity at a set depth. A slab can post a passing F1869 MVER reading and still carry an internal RH level that would fail a flooring manufacturer’s F2170 threshold, because the surface has dried faster than the slab core.
This matters most in a dispute. If a flooring failure occurs and the installer’s documentation shows an F1869 result while the manufacturer’s warranty required F2170 data, that mismatch alone can void coverage regardless of what the numbers actually say. The fix is procedural, not mathematical: confirm the required method in writing before testing, and never submit one test’s results as evidence of compliance with the other standard.
Getting It Right: Testing, Documentation, and Independent Verification
Moisture testing and floor flatness testing solve the same underlying problem from different angles: both replace a guess with a measured, documented number before the floor covering or racking system goes down. A slab can be perfectly flat under ASTM E1155 and still fail a floor covering installation if its moisture condition doesn’t match spec, just as a slab with acceptable moisture readings can still throw off automated guided vehicles or very narrow aisle racking if its FF/FL numbers are out of tolerance. Neither discipline substitutes for the other, and neither should be skipped to save a day of schedule.
Independent, third-party documentation matters for both. A testing firm with no product or installation stake in the outcome has no reason to round a probe reading in either direction, and that neutrality is what holds up when a warranty claim or a contract dispute lands on someone’s desk months after the concrete has cured.
Need an independent read on slab moisture or flatness before your flooring installation starts?
Frequently Asked Questions
What is the main difference between ASTM F2170 and F1869?
ASTM F2170 measures internal relative humidity within a concrete slab using probes placed at 40% of slab depth, reported as a percentage. ASTM F1869 measures moisture vapor emission rate at the slab surface using a calcium chloride dish sealed under plastic, reported in pounds per 1,000 square feet per 24 hours. They assess different aspects of slab moisture and are not interchangeable.
Can F1869 results be used to satisfy an F2170 spec requirement?
No. The two tests measure different physical properties at different locations in the slab and there is no accepted conversion between an MVER reading and a relative humidity percentage. Submitting F1869 data when a specification or warranty requires F2170 results does not demonstrate compliance and can jeopardize warranty coverage or contractual acceptance.
Is calcium chloride testing still valid for all concrete types?
Calcium chloride testing under ASTM F1869 has been removed as an acceptable method for lightweight concrete. ASTM developed F2170 in-situ relative humidity testing specifically to address lightweight and structural concrete assessment. F1869 remains in use for some conventional-weight concrete applications where a governing specification still calls for it.
How long does an ASTM F2170 test take to complete?
ASTM F2170 requires a minimum 24-hour equilibration period after probes are inserted into drilled holes, before a hygrometer reading is taken. Total project timelines vary depending on the number of probe locations required and slab access, but the 24-hour equilibration window is a fixed minimum under the standard.
How many probe locations does ASTM F2170 require?
ASTM F2170 field practice calls for a minimum of three probe locations for the first 1,000 square feet of slab, with one additional probe location for each additional 1,000 square feet. Larger slabs require proportionally more test locations to account for moisture variability across the pour.
Do flooring manufacturers require a specific moisture test method?
Many flooring and adhesive manufacturers now require or prefer ASTM F2170 relative humidity data for warranty coverage, particularly on moisture-sensitive systems and lightweight concrete. Requirements vary by manufacturer and product line, so the specific warranty documentation for the flooring or adhesive system in use should be reviewed before testing begins.
What happens if the wrong moisture test is used on a project?
Using a test method that doesn’t match the governing specification or manufacturer warranty requirement can void warranty coverage, create disputes over spec compliance, and leave a project without valid documentation if a flooring failure occurs later. Confirming the required test method in writing before testing begins avoids this risk.
Sources
- ASTM International, F2170-17 Standard Test Method for Determining Relative Humidity in Concrete Slabs Using in situ Probes, https://store.astm.org/f2170-17.html
- IFTI, “ASTM F2170 vs F1869: Which Concrete Moisture Test Is Right?” https://ifti.com/astm-f2170-vs-f1869-choosing-the-right-concrete-moisture-test-method-2/
- IFTI, “ASTM F2170 vs F1869: Which Moisture Test Fits Your Project?” https://ifti.com/astm-f2170-vs-f1869-which-moisture-test-fits-your-project/
- IFTI, “The ASTM F1869 Calcium Chloride Test: What It Measures, Its Limits” https://ifti.com/astm-f1869-calcium-chloride-test-guide/
- ConcreteMoisture.com, “RH Testing Practices” https://www.concretemoisture.com/contractors/rh-testing-practices/
- ConcreteMoisture.com, “Lightweight Concrete Moisture Testing” https://www.concretemoisture.com/architects/understanding-lightweight-concrete-works/
- Protimeter, “The ASTM F-2170, Concrete Moisture Testing & Compliance” https://blog.protimeter.com/blog/astmf2170-regulation-concrete-rh-testing
- WJ Grosvenor, “Limitations of the Calcium Chloride Moisture Test” https://www.wjgrosvenor.com/limitations-of-the-calcium-chloride-moisture-test/
- Tnemec Company, Inc., “3 Ways to Test Concrete Moisture” https://tnemec.com/remedy-index-page/3-ways-test-concrete-moisture/
- ASTM F1869 Information, https://www.f1869.org/
- f2170.org, “The New Standard for Lightweight Concrete” https://www.f2170.org/rh-testing-the-new-standard-for-lightweight-concrete/
This article is for general informational purposes only and does not constitute engineering, legal, or product-specific advice. Flatness, levelness, and moisture requirements and results vary by project, specification, and site conditions. Consult IFTI and refer to current ASTM (e.g., E1155, F2170, F1869) and ACI standards for project-specific guidance.