F2170 vs. F1869 at a Glance
ASTM F2170 measures internal relative humidity inside a concrete slab using in-situ probes, while ASTM F1869 measures surface moisture vapor emission rate using anhydrous calcium chloride. They test different physical conditions, report results in different units, and are governed by separate ASTM standards with separate acceptance criteria set by the flooring or adhesive manufacturer.
Every year IFTI fields calls from GCs and engineers holding a moisture test report that doesn’t match what the flooring manufacturer’s data sheet actually requires. Usually the crew ran the test they’d always run, not the one the spec called for. That single mismatch can delay a slab schedule by weeks while a second test is arranged and the concrete conditions have to be re-verified as representative. The table below is the fastest way to confirm you’re looking at the right method before probes or CaCl dishes ever go down.
| Factor | ASTM F2170 | ASTM F1869 |
|---|---|---|
| What it measures | Relative humidity inside the slab, at depth | Rate of moisture vapor emitted from the slab surface |
| Reported result | Percent RH (e.g., 75%, 80%, 85%) | lb of moisture per 1,000 sq ft per 24 hours |
| Test mechanism | In-situ probes inserted into drilled holes, sealed and left to equilibrate | Anhydrous calcium chloride dish sealed under a dome on the slab surface |
| Typical duration | Probes equilibrate approximately 24 hours before reading; single reading taken | Traditional exposure period of 60 to 72 hours |
| Acceptance criteria source | Set by the flooring/adhesive/coating manufacturer, not ASTM | Set by the flooring/adhesive/coating manufacturer, not ASTM |
| Lightweight concrete | Recognized in-situ alternative for lightweight mixes | Amended to exclude calcium-chloride testing as acceptable for lightweight concrete |
| Key limitation | Only reflects conditions at probe depth and location tested | Only reflects surface-level emission at time of test; sensitive to ambient conditions during exposure |
What ASTM F2170 Actually Measures: Internal Relative Humidity
ASTM F2170 is the standard test method for “quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests,” according to ASTM International’s F2170 standard. It captures moisture conditions inside the slab, which is where moisture-related flooring failures usually originate.
The test works by drilling holes to a specified depth, inserting sealed probes, and allowing them to equilibrate with the surrounding concrete before taking a reading. Probe depth is not arbitrary. Per the ASTM F2170 technical information site, probes are typically placed at approximately 40% of slab depth when the slab dries from one side only (the common case for slab-on-grade with a vapor retarder below) and approximately 20% of slab depth when the slab dries from two sides (as with some suspended or elevated slabs). Get the drying direction wrong and the probe reading won’t represent the moisture gradient the flooring will actually sit against.
Results are reported as a percent RH value, full stop. There’s no ASTM-mandated pass/fail threshold. An 85% RH reading isn’t automatically a failure; it’s only a failure if the specific flooring adhesive or coating’s technical data sheet sets a maximum RH below 85%. That distinction matters because two products installed on the same slab can have entirely different RH limits.
What ASTM F1869 Actually Measures: Surface Vapor Emission
ASTM F1869 is the standard test method for “quantitative determination of the rate of moisture vapor emitted from below-grade, on-grade, and above-grade (suspended) bare concrete floors,” per ASTM International’s F1869-22 standard, with the scope confirmed again in the F1869-23 listing. This test targets what’s leaving the surface, not what’s happening deeper in the slab.
A dish of anhydrous calcium chloride is weighed, exposed under a sealed dome on the clean, prepared slab surface, and reweighed after the exposure period, traditionally 60 to 72 hours. The calcium chloride’s weight gain, converted to a rate, produces the result: pounds of moisture per 1,000 square feet per 24 hours. A commonly referenced legacy limit in older flooring specs is 3 lb/1,000 ft²/24 h, though the actual acceptable value again comes from the manufacturer’s current technical documentation, not from ASTM itself.
Because F1869 is a surface test with a multi-day exposure window, it’s more exposed to ambient conditions during the test than a single-point RH reading. Ambient RH swings, HVAC cycling on and off, or a dome disturbed mid-test can all skew the result.
When to Choose F2170
Choose F2170 when the flooring, adhesive, or coating manufacturer’s current technical data sheet specifies a maximum RH percentage, when the project involves thick industrial slabs where moisture gradients through the depth matter, or when the concrete is a modern mix design without an approved calcium-chloride method. F2170 is the more common default for contemporary resilient flooring and adhesive systems.
- The manufacturer’s spec sheet states an RH limit (e.g., “install only when RH is 80% or below”).
- The slab is thick, and moisture distribution through the cross-section is a legitimate concern, such as high-bay warehouse and manufacturing floors.
- Multiple probe locations are needed to map RH variation across a large placement, near joints, or near exterior walls and plumbing penetrations.
- The project specification or owner’s warranty explicitly references ASTM F2170.
When to Choose F1869
Choose F1869 when the manufacturer’s documentation or an existing project specification explicitly calls for an MVER result in lb/1,000 ft²/24 h, when a legacy specification hasn’t been formally updated to an RH-based requirement, or when a warranty claim history requires the calcium-chloride method for consistency with prior testing on the same building.
- The current adhesive, coating, or flooring technical data sheet states a maximum lb/1,000 ft²/24 h value rather than an RH percentage.
- An older project specification was written strictly around F1869 and has not been revised.
- The concrete is a standard-weight mix with no lightweight aggregate restrictions on the calcium-chloride method.
- A facility owner’s established testing protocol for a portfolio of buildings has historically used F1869 and consistency across buildings is the priority.
Why You Can’t Substitute One Test for the Other
F2170 and F1869 measure different physical phenomena at different locations in the slab, using different units, so no valid conversion exists between them. An RH percentage from F2170 cannot be translated into an equivalent lb/1,000 ft²/24 h figure from F1869, and vice versa. Running the “wrong” test and converting the number is not a substitute for running the specified test.
Field error to avoid: There is no valid conversion between an RH percentage and an MVER value. An “85% RH” result is not equivalent to “3 lb/1,000 ft²/24 h,” and treating one as a stand-in for the other is one of the most common and costly mistakes on moisture-sensitive flooring projects.
This error shows up most often when a contractor has probes and RH meters on hand from a previous job but the current manufacturer’s data sheet specifies MVER, or the reverse. Running the test you have equipment for, instead of the test the manufacturer requires, produces a report an inspector or warranty administrator can reject outright, even if the number “looks fine.” If a specification, manufacturer requirement, and warranty document don’t all point to the same test method, that conflict needs written resolution before any test is scheduled, not after.
Special Case: Lightweight Concrete
Lightweight concrete requires special handling because calcium-chloride testing under F1869 is no longer an acceptable method for it. Per the ASTM F1869 technical information site, F1869 was amended specifically to remove calcium-chloride testing as an acceptable method for measuring moisture in lightweight concrete, and F2170 was developed in part to give the industry an in-situ RH alternative recognized for that application.
The practical implication: if your slab uses lightweight aggregate, don’t default to F1869 out of habit or because it’s what the crew has always run. Confirm with the flooring or adhesive manufacturer which method their current data sheet approves for lightweight mixes, and expect that answer to point toward F2170 or another manufacturer-endorsed in-situ method. Lightweight slabs also tend to hold moisture longer during curing, which affects testing timeline expectations regardless of which method is used.
Recommended Decision Process for Engineers and GCs
The correct test is determined by working backward from the finish system’s current documentation, not by defaulting to whichever test method the crew is most familiar with. Following a fixed sequence before any probe or dish goes down avoids the rework of an unusable report.
- Identify the exact finish system. Note the specific flooring product, adhesive, and coating or underlayment, including manufacturer and product line.
- Pull the current technical data sheet for each product. Data sheets get revised; confirm you’re reading the current edition, not a printout from a previous job.
- Check the concrete type. Confirm standard-weight versus lightweight aggregate before selecting a method.
- Confirm the applicable ASTM standard edition. F1869 and F2170 have been revised over time; the project spec should reference a current edition.
- Map test locations and probe depths (for F2170) or dish placement (for F1869) according to slab drying direction, thickness, joints, and proximity to plumbing or exterior walls.
- Confirm building environmental conditions match the manufacturer’s testing prerequisites: enclosed and weather-tight, HVAC operating at intended service conditions, ambient temperature and RH stabilized, and adequate slab curing age.
- Run the specified method exactly as written. Don’t substitute equipment, exposure time, or probe depth to save a site visit.
- Do not proceed with installation on a failed or noncomparable result. Escalate to the manufacturer and design team rather than reinterpreting the number.
- Document everything for closeout. Test method, edition, dates, environmental conditions at time of test, probe/dish locations, and raw results all belong in the project record supporting the warranty.
Practical Selection Guide
This table maps common project conditions to the test method most likely to be correct as a starting point. It does not replace confirmation against the specific manufacturer’s current data sheet for a given project.
| Project Condition | Preferred Starting Test |
|---|---|
| Manufacturer data sheet specifies a maximum RH percentage | ASTM F2170 |
| Manufacturer data sheet specifies a maximum lb/1,000 ft²/24 h value | ASTM F1869 |
| Lightweight concrete slab | Verify manufacturer-approved method (typically F2170) |
| Thick industrial slab with moisture gradient concerns | ASTM F2170 |
| Existing spec written only in lb/1,000 ft²/24 h, not formally revised | ASTM F1869 unless the spec is formally revised |
| Warranty document requires both test results | Perform both F2170 and F1869 |
| Manufacturer spec and project spec conflict on method | Obtain written clarification before testing |
Both methods only produce a usable result if the building itself is in a representative state at test time. That means the structure is enclosed and weather-tight, HVAC is running at the conditions intended for occupancy, ambient temperature and RH have stabilized, the slab has cured long enough to reflect real-world drying, and any grinding, shot-blasting, sealers, or curing compounds applied to the surface are accounted for, since these can suppress or distort readings on either test. A slab tested too early, in an unconditioned building, or right after a surface treatment can produce a result that has nothing to do with how the floor will behave once it’s occupied.
A slab that passes its moisture test but is out of tolerance on flatness and levelness still isn’t ready for flooring installation. IFTI’s core independent testing includes the elevation survey of the slab and moisture verification under F2170 or F1869, the two checks we help project teams run before committing to an installation date. Getting the slab flat, level, and moisture-appropriate before flooring goes down is what avoids the grinding, shimming, and re-pours that eat schedules and budgets.
Not sure which moisture test your project spec actually requires, or need it run and documented correctly alongside a flatness check?
Frequently Asked Questions
Is ASTM F2170 more accurate than ASTM F1869?
Neither test is more accurate than the other; they measure different physical conditions. F2170 measures internal relative humidity at probe depth inside the slab. F1869 measures surface moisture vapor emission rate. The correct test is the one specified by the flooring, adhesive, or coating manufacturer’s current technical documentation, not the one considered more precise in general.
Can I convert an F2170 RH percentage into an F1869 MVER value?
No valid conversion exists between an RH percentage from F2170 and an MVER value from F1869, since the two tests measure different phenomena at different locations in the slab using different units. Treating one result as equivalent to the other is a documented field error and can produce reports that don’t meet manufacturer or warranty requirements.
What RH percentage or MVER value counts as a passing result?
ASTM does not set a universal pass/fail threshold for either test. Acceptable limits are established by the specific flooring, adhesive, or coating manufacturer in their current technical data sheet, and can vary by product line. A result must be checked against the manufacturer’s documented limit for the exact product being installed.
Why can’t I use calcium-chloride testing on lightweight concrete?
ASTM F1869 was amended to remove calcium-chloride testing as an acceptable method for lightweight concrete, according to the ASTM F1869 technical information site. ASTM F2170 was developed in part to provide an in-situ relative humidity alternative recognized for that application, making it the typical starting point for lightweight slabs pending manufacturer confirmation.
How deep should F2170 probes be placed?
Per the ASTM F2170 technical information site, probes are typically placed at approximately 40% of slab depth for a slab drying from one side only, and approximately 20% of slab depth for a slab drying from two sides. Correct probe depth depends on knowing the slab’s drying condition before testing begins.
What building conditions need to be in place before running either moisture test?
Both tests require the building to be enclosed and weather-tight, with HVAC operating at intended service conditions, stabilized ambient temperature and RH, adequate slab curing age, and awareness of any surface treatments such as grinding, shot-blasting, sealers, or curing compounds. Testing before these conditions are met can produce results that don’t represent actual in-service moisture behavior.
What should I do if a moisture test result fails the manufacturer’s limit?
Do not proceed with installation on a failed or noncomparable result. Escalate the result to the flooring or adhesive manufacturer and the project’s design team to determine next steps, which may include additional drying time, a mitigation system, or re-testing once conditions change. Document the failed result and all follow-up actions for the project closeout record.
Sources
- ASTM International, “ASTM F1869-22, Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride” (2022)
- ASTM International, “ASTM F2170, Standard Test Method for Determining Relative Humidity in Concrete Floor Slabs Using In-Situ Probes” (F2170-19a listing, 2020)
- ASTM International, “ASTM F1869-23 product listing” (2023)
- ASTM International, “ASTM F2170-19a product listing” (2020)
- ASTM F1869 technical information site, “Calcium Chloride Testing and Lightweight Concrete Limitations” (2018)
- ASTM F2170 technical information site, “In-Situ Probe Placement Guidance” (undated)
This article is for general informational purposes only and does not constitute engineering, legal, or product-specific advice. Flatness and levelness (and moisture) requirements and results vary by project, specification, and site conditions. Consult IFTI and refer to current ASTM (e.g., E1155, F2170, F1869) and ACI standards for project-specific guidance.